LET'S TALK

EDGE XP10 Power Block

The EDGE XP10 Power Block is a state-of-the-art switchboard and UPS featuring modularized critical components and delivers a configurable conditioned power supply.

Unit PUE Range

As low as 1.15 (Dependent upon Environmental and Operational conditions)

Maximum Power Delivery

(2) High Efficiency Uninterruptible Power Supplies (UPS) provides conditioned Uninterruptible AC power

Critical IT Capacity
Maximum Available kW

@N

1500 kVA (Two UPSs at 750 kVA each)

@N+1

750 kW

@2N

750 kW

Ride Through (Load Specific)

5 minutes at 100%

Security

Access Control

Open Compartmentalized Architecture, Enhanced Security Encryption, Versatile Interoperability, Proximity Card Readers (Keypad and Biometric Options Available), Layers of Physical & Logical Protection, Separate IT & Support Space Access

Camera

Pre-Wired for IP Based Camera

Door Locks

Electronic Locks

Fire System

Dedicated Fire System

Externally Accessible Fire Control Panel, Pre-Discharge Alarm & Strobe Lights, Fire Pull Station, Abort Hold Button and Keyed Bottle Disconnects

Smoke Detection

Aspirating Smoke Detection

Fire Suppression

Clean Agent Fire suppression (Non-Ozone Depleting Agent)

Fire Rating

NFPA 72 Compliant and UL-Listed Fire Equipment

Exterior
Dimensions
US(Metric)

Length Width Height

42’ 8” (13.0 m) 11’ 8” (3.5 m) 13’ 5” (4.0 m)

Interior Tech
Space Dimensions
US(Metric)

Length Width Height

42′ 0″ (12.8 m) 11’ 0” (3.3 m) 8’ 5-1/2” (2.6 m)

Estimated Module Shipping Weight
US(Metric)

78,000 Lbs (35.380 kg) (Excludes Storage Batteries)

Input Power
Voltage/Frequency 

480V, 3 Phase, 60Hz
400V, 3 Phase, 50Hz

UPS Type

Online, Double-Conversion, Transformer Free, Insulated-Gate Bipolar Transistor (IGBT) with Pulse-Width Modulation

UPS Energy Storage

VRLA Battery Strings, Lithium Ion (Optional)

Cooling Type

(2) 50 kW Chilled Water, (CRAH) Computer Room Air Handling Units (Standard); DX, (CRAC) Computer Room Air Conditioning Units (Optional)

Leak Detection

Spot Leak Detection