EDGE XP10 Power Block
The EDGE XP10 Power Block is a state-of-the-art switchboard and UPS featuring modularized critical components and delivers a configurable conditioned power supply.
Unit PUE Range
As low as 1.15 (Dependent upon Environmental and Operational conditions)
Maximum Power Delivery
(2) High Efficiency Uninterruptible Power Supplies (UPS) provides conditioned Uninterruptible AC power
Critical IT Capacity
Maximum Available kW
@N
1500 kVA (Two UPSs at 750 kVA each)
@N+1
750 kW
@2N
750 kW
Ride Through (Load Specific)
5 minutes at 100%
Security
Access Control
Open Compartmentalized Architecture, Enhanced Security Encryption, Versatile Interoperability, Proximity Card Readers (Keypad and Biometric Options Available), Layers of Physical & Logical Protection, Separate IT & Support Space Access
Camera
Pre-Wired for IP Based Camera
Door Locks
Electronic Locks
Fire System
Dedicated Fire System
Externally Accessible Fire Control Panel, Pre-Discharge Alarm & Strobe Lights, Fire Pull Station, Abort Hold Button and Keyed Bottle Disconnects
Smoke Detection
Aspirating Smoke Detection
Fire Suppression
Clean Agent Fire suppression (Non-Ozone Depleting Agent)
Fire Rating
NFPA 72 Compliant and UL-Listed Fire Equipment
Exterior
Dimensions
US(Metric)
Length Width Height
42’ 8” (13.0 m) 11’ 8” (3.5 m) 13’ 5” (4.0 m)
Interior Tech
Space Dimensions
US(Metric)
Length Width Height
42′ 0″ (12.8 m) 11’ 0” (3.3 m) 8’ 5-1/2” (2.6 m)
Estimated Module Shipping Weight
US(Metric)
78,000 Lbs (35.380 kg) (Excludes Storage Batteries)
Input Power
Voltage/Frequency
480V, 3 Phase, 60Hz
400V, 3 Phase, 50Hz
UPS Type
Online, Double-Conversion, Transformer Free, Insulated-Gate Bipolar Transistor (IGBT) with Pulse-Width Modulation
UPS Energy Storage
VRLA Battery Strings, Lithium Ion (Optional)
Cooling Type
(2) 50 kW Chilled Water, (CRAH) Computer Room Air Handling Units (Standard); DX, (CRAC) Computer Room Air Conditioning Units (Optional)
Leak Detection
Spot Leak Detection