EDGE XA20 Modular Data Center
Outdoor or Indoor Deployable Modular Data Center.
- Delivers up to 600 kW of Critical IT power and Economized Cooling for up to thirty-five (35) 52U Cabinets @ N
- Engineered to meet NEMA 4 compliance standards for deployment in all global environments
Unit PUE Range
As low as 1.05 (Dependent upon Environmental and Operational conditions)
Maximum Module Capacity
Maximum Available kW at 25 °F ΔT
@N
600 kW
@N+1
500 kW
@2N
300 kW
Maximum Module Density, kW/Cabinet
(35) 24″ (609 mm) Cabinets
@N
17.1 kW/Cabinet
@N+1
14.3 kW/Cabinet
@2N
8.5 kW/Cabinet
Security
Access Control
Open Compartmentalized Architecture, Enhanced Security Encryption, Versatile Interoperability, Proximity Card Readers (Keypad and Biometric Options Available), Layers of Physical & Logical Protection, Separate IT & Support Space Access
Camera
IP Based Camera
Door Locks
Electronic Locks
Fire System
Dedicated Fire System
Externally Accessible Fire Control Panel, Pre-Discharge Alarm & Strobe Lights, Fire Pull Station, Abort Hold Button and Keyed Bottle Disconnects
Smoke Detection
Intelligent Photoelectric Smoke Sensors
Fire Suppression
Clean Agent Fire suppression (Non-Ozone Depleting Agent)
Fire Rating
NFPA 72 Compliant and UL-Listed Fire Equipment
Exterior
Dimensions
US(Metric)
Length Width Height
42’ 8” (13.0 m) 33′ 6″ (10.2 m) 13’ 3” (4.0 m)
Interior Tech
Space Dimensions
US(Metric)
Length Width Height
41’ 8” (12.7 m) 21’ 0” (6.4 m) 9’ 4” (2.8 m)
IT Space
Area (Usable)
US(Metric)
645 ft2 (60 m2)
Technology-agnostic design with 645 ft2 of IT space.
Cold Aisle = 52″ (1.3 m), Hot Aisle = 36″ (.91 m) (Standard Configuration)
Estimated Module Shipping Weight
US(Metric)
101,000 lbs. (45,812 kg) (Includes IT and Cooling Blocks)
(Excludes IT Cabinets and Equipment)
Standard
IT Cabinets
(Quantity)
(35) 24” (609 mm) Cabinets (Up to 52U)
Voltage/
Frequency/
Amperage
400 V, 3-Phase, 50 Hz 480 V, 3-Phase, 60 Hz
Power
Distribution Unit
400 A Busways Standard; Up to 800 A per Busway (Optional)
Cooling Type
Outside Air (OSA) Economizer with Chilled Water Trim, Counterflow Chilled Water Coils and High Efficiency Plug Fans with Electronically Commutated Motors (ECM)
Leak Detection
Strip Leak Detection