BASELAYER® EDGE

XA30 Modular Data Center

LET'S TALK

EDGE XA30 Modular Data Center

Outdoor or Indoor Deployable Modular Data Center.

  • Delivers up to 600 kW of Critical IT power and Economized Cooling for up to sixty (60) 52U Cabinets @ N
  • Engineered to meet NEMA 4 compliance standards for deployment in all global environments
Unit PUE Range

As low as 1.05 (Dependent upon Environmental and Operational conditions)

Maximum Module Capacity
Maximum Available kW at 25 °F ΔT

@N

600 kW

@N+1

500 kW

@2N

300 kW

Maximum Module Density, kW/Cabinet
(60) 24″ (609 mm) Cabinets

@N

10 kW/Cabinet

@N+1

8.3 kW/Cabinet

@2N

5.0 kW/Cabinet

Security

Access Control

Open Compartmentalized Architecture, Enhanced Security Encryption, Versatile Interoperability, Proximity Card Readers (Keypad and Biometric Options Available), Layers of Physical & Logical Protection, Separate IT & Support Space Access

Camera

Pre-wired for IP Based Camera

Door Locks

Electronic Locks

Fire System

Dedicated Fire System

Externally Accessible Fire Control Panel, Pre-Discharge Alarm & Strobe Lights, Fire Pull Station, Abort Hold Button and Keyed Bottle Disconnects

Smoke Detection

Aspirating Smoke Detection

Fire Suppression

Clean Agent Fire suppression (Non-Ozone Depleting Agent)

Fire Rating

NFPA 72 Compliant and UL-Listed Fire Equipment

Exterior
Dimensions
US(Metric)

Length Width Height

42’ 8” (13.0 m) 44’ 0” (13.4 m) 13′ 3″ (4.0 m)

Interior Space
Dimensions
US(Metric)

Length Width Height

41’ 8” (12.7 m) 31’ 6” (9.7 m) 9’ 4” (2.8 m)

IT Space
Area (Usable)
US(Metric)

1083 ft2 (101.9 m2)
Technology-agnostic design with 1083 ft2 of IT space. Cold Aisle = 52″ (1.3 m), Hot Aisle = 36″ (.91 m) (Standard Configuration)

Estimated Module Shipping Weight
US(Metric)

124,000 lbs. (56,245 kg) (Includes IT and Cooling Blocks)
(Excludes IT Cabinets and Equipment)

Standard
IT Cabinets
(Quantity)

(60) 24” (609 mm) Cabinets (Up to 52U)

Voltage/
Frequency/
Amperage

400 V, 3-Phase, 50 Hz 480 V, 3-Phase, 60 Hz

Power
Distribution Unit

400 A Busways Standard; Up to 800 A per Busway (Optional)

Cooling Type

Outside Air (OSA) Economizer with Chilled Water Trim, Counterflow Chilled Water Coils and High Efficiency Plug Fans with Electronically Commutated Motors (ECM)

Leak Detection

Strip Leak Detection