CORE C20 DATA MODULE
The CORE C20 Data Module is a state-of-the-art, compartmentalized, raised floor data center space that delivers standardized increments of predictable capacity.
- Delivers up to 500 kW of Critical IT power and cooling for up to fifty (50) 50U Cabinets @ N
- Technology-agnostic design with 994 square feet (92.4 m2) of available IT space
Unit PUE Range
As low as 1.15 (Dependent upon Environmental and Operation Conditions)
Maximum Module
Capacity
Maximum Available
kW at 25 °F ∆T
@N
500kW
@N+1
450kW
@2N
200kW
Maximum Module Density, kW/Cabinet
(50) 24″ (609 mm) Cabinets
Outside Rows (36)
Center Row (14)
@N
12.0 kW/Cabinet
4.0 kW/Cabinet
@N+1
11.0 kW/Cabinet
4.0 kW/Cabinet
@2N
4.0 kW/Cabinet
4.0 kW/Cabinet
Security
Access Control
Open Compartmentalized Architecture, Enhanced Security Encryption, Versatile Interoperability, Proximity Card Readers (Keypad and Biometric Options Available), Layers of Physical & Logical Protection, Separate IT & Support Space Access
Camera
IP Based Camera
Door Locks
Electronic Locks
Fire System
Dedicated
Fire System
Externally Accessible Fire Control Panel, Pre-Discharge Alarm & Strobe Lights, Fire Pull Station, Abort Hold Button and Keyed Bottle Disconnects
Smoke Detection
Intelligent Photoelectric Smoke Sensors
Fire Suppression
Clean Agent Fire suppression (Non-Ozone Depleting Agent)
Fire Rating
NFPA 72 Compliant and UL-Listed Fire Equipment
Exterior
Dimensions
US(Metric)
Length Width Height
42’ 8” (13.0 m) 23’ 4” (7.1 m) 13’ 5” (4.0 m)
Interior
Dimensions
US(Metric)
Length Width Height
42’ 0” (12.8 m) 22’ 0” (6.7 m) 8’ 5-1/2” (2.6 m)
Interior IT
Space Area
US(Metric)
994 ft2 (92.3 m2)
Technology-agnostic design with 994 ft2 of IT space. Cold Aisle = 4′ (1.2 m), Hot Aisle = 3’6″ (1.0 m)
Estimated Module Shipping Weight
US(Metric)
104,000 lbs (47,174 kg) (Excludes IT equipment and cabinets)
Standard
IT Cabinets
(Quantity)
(50) 24” (609 mm) Cabinets (Up to 50U) (38) 30” (762 mm) Cabinets (Up to 50U)
Voltage/
Frequency/
Amperage
480 V, Three-Phase, 60 Hz/400 A 400 V, Three-Phase, 50 Hz/400 A
Incoming
Power Feeds
Configurable Up To (8) 480 V, 400 A, 60 Hz, 3-phase or (8) 400 V, 400 A, 50 Hz, 3-phase. Two 400 A feeds per PDU
Power
Distribution Unit
(4) 200 kVA PDUs
Cooling Type
Chilled Water, Air Handling Units (AHU)
Leak Detection
Spot Leak Detection